USED 2001 PIONEER TRANSFORMERS G2112B1411
Overview
Specs
kVA: 11870 kVA
Primary Voltage: 25000 volts
Secondary Voltage: 4160/2400 volts
Phase: 3-phase
Transformer Type: Power Transformer
Auto VS Isolation: Isolation
Oil vs Dry: Oil
Frequency: 60 Hz
Cooling Class: ONAN / ONAF
Connection: HV: Delta, LV: Wye
Impedance: 6.09 % at 7.50 MVA
Full wave impulse level: HV: 125 kV, LV: 60 kV
Insulation Class: 65 °C rise
Coolant: Non-PCB, Class B, Type I, Mineral Oil
Tank will withstand full vacuum: yes